IM260 PROFIBUS-DP Interface Module
IM260 is used on PROFIBUS-DP interface distributed I/O system,
optoelectronic isolation, stable performace
Support 300 CPU with DP Master function,
RS 485 communication baud rate from 9.6Kbs to 12Mbs adjusting automatically,
Max. supports 99 slaves connecting,
Adopts Optoelectronic isolation and over-current protection on RS 485 end,
Power supply has reverse connection protection and surge absoption.
Voltage range |
20.4-28.8V DC |
Interface |
1 RS485 port |
Connection protocol |
PROFIBUS-DP |
Station address setting | 0 to 99(by knob switch) |
Max. stations per period | 32 |
Max. station per net |
126, Max. to 99 IM260 stations |
PROFIBUS-DP communication speed ( setting automatically) |
9.6、19.2、45.45、93.75、187.5 and 500Kbps 1.5、3、6 and 12Mbps |
UN 200 Modules Mo. | 7 |
Cable length |
|
< 93.75Kbps |
1200meters |
187.5Kbps |
1000meters |
500Kbps |
400meters |
1-1.5Mbps |
200meters |
3-12Mbps |
100meters |
24VDC input power | |
-Voltage range | 20.4-28.8V DC |
-Max.Current | 2A peak |
24VDC power of port | |
-Voltage range | 20.4-28.8V DC |
-Output current | 300mA(Max.) |
Isolation | No isolation,circuit is same as input 24V DC circuit |
Dimension |
71*80*62mm |