EM AT04
Model No.
EM AT04
Order No.
UN 288-3AT04-0AA0
Side View
technical parameters
model | EM AT04 |
order number | UN 288-3AT04-0AA0 |
conventional | |
Dimensions W x H x D (mm) | 45×100×81 |
weight | 125g |
power consumption | 1.5W |
Current Consumption (SM Bus) | 80 mA |
Current consumption (24 V DC) | 40 mA |
analog input | |
Input channels | 4 |
Resolution temperature resistance |
0.1 ˚C / 0.1 ˚F 15 digits + sign |
maximum withstand voltage | ±35V |
noise suppression | 85 dB for selected filter setting (10 Hz, 50 Hz, 60 Hz or 400 Hz) |
common mode rejection | >120 dB at 120 V AC |
impedance | ≥ 10 MΩ |
Isolate field side from logic side field side from 24 V DC side 24 V DC side from logic side |
500 VAC 500 VAC 500 VAC |
Channel-to-channel isolation | - |
precision | Please refer to the thermocouple selection table |
repeatability | ± 0.05 % FS |
Measuring principle | Integral type |
Module update time | See filter selection table |
Cold junction temperature error | ± 1.5 ° C |
Cable length (maximum) | Maximum length to sensor is 100 m |
Cable resistance | 100Ω max. |
diagnosis | |
overflow/underflow | √ |
Open circuit (current mode only) | √ |
24 V DC low voltage | √ |