physical properties
|
Dimensions (W*H*D)
|
196 x 80 x 62mm
|
Power consumption
|
10W
|
17W
|
Power characteristics
|
Rated voltage
|
DC 24V
|
AC 220V
|
Input voltage
|
DC 20.4 to 28.8V
|
AC 85 to 264V
|
Input Current
|
100mA (CPU only, at 24VDC)
|
60/30mA (CPU only, 120/240VAC)
|
electric shock
|
12A at 28.8V DC
|
20A at 264V AC
|
Insurance
|
3A 250V slow melting
|
3A 250V slow melting
|
sensor voltage
|
L + minus 5V
|
20.4 to 28.8VDC
|
sensor current
|
300mA (max)
|
300mA (max)
|
Ripple noise
|
from input power
|
Less than 1V peak fraction
|
Memory characteristics
|
program memory
|
18K
|
data storage
|
10K
|
General Features
|
Total number of timers
|
256 in total, 4 1ms, 16 10ms, 236 100ms
|
Total number of counters
|
256
|
time interruption
|
2 1ms resolution
|
edge interrupt
|
4 rising edges/4 falling edges
|
Analog potentiometer
|
not support
|
Real Time Clock
|
Supported, 50 hours/typ. (minimum 8 hours at 40°C) after power down
|
Card Options
|
memory card, battery card
|
Power-down retention
|
Supported ( data retention up to 10 years )
|
Ethernet communication function
|
interface
|
1 RJ45 Ethernet port
|
communication rate
|
10/100Mb/s
|
duplex mode
|
full duplex
|
Communication distance
|
Twisted pair 100m (more than router or switch)
|
Maximum number of simultaneous connections
|
7 (MODBUS-TCP + S7)
|
The maximum number of bytes of single communication
|
240 bytes
|
Host computer communication
|
Support Micro/Win Kingview WinCC
|
UniMAT HMI screen
|
Supports up to 2 (S7 communication)
|
Modbus master/slave
|
Supports 4 master/4 slave simultaneous connections
|
Serial communication function
|
interface
|
2 RS-485 standard PPI communication ports
Support Freeport and MODBUS communication
|
Communication baud rate
|
PPI: 9.6, 19.2, 187.5kbps three baud rates
Free port: 1.2kbps~115.2kbps
|
Maximum length of each cable length
|
With isolated interruption relays: 187.5kbps up to 1000 meters, 38.4kbps up to 1200 meters, 50 meters without isolated repeaters
|
Maximum number of sites
|
32 stations per segment, 126 stations per network
|
Maximum number of master stations
|
32
|
PPI master mode
|
support
|
I/O Characteristics
|
Local digital input
|
24 inputs
|
Local digital output
|
16 outputs
|
Local analog input
|
none
|
Local analog output
|
none
|
Digital I/O Image Area
|
256 ( 128 in / 128 out)
|
Analog I/O image area
|
64 ( 32 in / 32 out)
|
Maximum allowable expansion I/O modules
|
7 modules
|
Digital Input Characteristics
|
The number of digital input points integrated in the machine
|
24 inputs
|
input type
|
PNP/NPN
|
Rated voltage
|
24VDC, 4mA
|
Maximum continuous allowable voltage
|
30V DC
|
surge voltage
|
35VDC, 0.5 seconds
|
logic 1 [minimum]
|
15VDC 2.5mA
|
logic 0[max]
|
5VDC 1mA
|
input filter
|
1-13ms
|
Allowable leakage current [max]
|
1mA
|
isolation
|
is opto-isolated
|
Optical isolation
|
500VAC for 1 minute
|
high-speed counter
|
Single-phase 20K[2 pieces]
|
AB phase 10K[1]
|
Digital output characteristics
|
Local integrated digital output points
|
16 outputs
|
output type
|
Solid State - MOSFET
|
dry contact
|
Rated voltage
|
24VDC
|
24VDC or 250VAC
|
voltage range
|
20.4~28.8VDC
|
5~30VDC 5~250VAC
|
Inrush current (max)
|
8A, 100ms
|
5A 4s 10% duty cycle
|
logic 1 (minimum)
|
20VDC (at maximum current)
|
-
|
logic 0 (max)
|
0.1VDC, 10KΩ load
|
-
|
Rated current per point (max)
|
0.75A
|
2A
|
Current rating per common (max)
|
6A
|
10A
|
Leakage current [max]
|
10uA
|
-
|
Lamp load [max]
|
5W
|
30W DC/200W AC
|
Inductive clamping voltage
|
L+ minus 48VDC 1W power consumption
|
-
|
On-resistance [contact]
|
0.3Ω typical (0.6Ω max)
|
0.2Ω (max when new)
|
Pulse frequency [max]
|
20kHz 2 [Q0.0 Q0.1]
|
1Hz
|
mechanical life cycle
|
-
|
10000000 (no load)
|
Contact life
|
-
|
100000 (rated load)
|
Two outputs in parallel
|
Yes, only when outputting the same group
|
no
|
Environmental parameters
|
Working temperature
|
0°C to +60°C (horizontal installation), 0°C to +40°C (vertical installation)
|
Transport ambient temperature
|
-20℃~+80℃
|
Ambient relative humidity
|
5 to 95%, non-condensing (RH class 2, in accordance with IEC61131-2)
|
Electromagnetic Compatibility
|
Noise suppression, in accordance with IEC61000-6-2
|
Mechanical class (vibration)
|
IEC60068,Part2-6/10up58Hz
|
Protection class
|
IP20
|