model
Technical Parameters
EM QR16
order number
UN 288-2QR16-0AA0
conventional
Dimensions W x H x D (mm)
45 x 100 x 81
power consumption
4.5W
Current Consumption (SM Bus)
110 mA
digital output
output points
16
type
relay, dry contact
voltage range
5~30V DC or 5~250V AC
Logic 1 signal at maximum current
-
Logic 0 signal with 10 KΩ load
-
Rated current per point (maximum)
2.0A
lamp load
30W DC/200W AC
On-state contact resistance
0.2 Ω max for new devices
Leakage current per point
-
Inrush current
7 A with contacts closed
overload protection
no
Isolation (field side and logic side)
1500 V AC
for 1 min (coil and contact) None (coil and logic side)
isolation resistance
100 MΩ minimum for new devices
Insulation between breaking contacts
750 V AC for 1 min
isolation group
4
Current per common (maximum)
8A
switch delay
up to 10 ms
Mechanical life (no load)
10,000,000
open/close cycles
Contact life under rated load
100,000 open/close cycles
Output status in STOP mode
previous value or replacement value (default is 0)
Simultaneously connected outputs
16
cable length
500 m (shielded), 150 m (unshielded)
Side View
Dimensions (mm)
Wiring Diagram
If You Would Like to Contact Support or Make a Purchase Please Fill out the Form
If you have urgent needs, please call our customer service number