Technical Parameters

model

EM DR32

order number

UN 288-2DR32-0AA0

Dimensions W x H x D (mm)

70 x 100 x 81

weight

295.4 g

Power consumption

10 W.

Current consumption (SM bus)

180 mA

Current consumption (24 V DC)

4 mA per input used

11 mA per relay coil used

digital input

Enter the number of points

16

type

sink/source

Rated voltage

24 V DC at 4 mA, nominal

allowable continuous voltage

30 V DC max

surge voltage

35 V DC for 0.5 s

Logic 1 signal (minimum)

15 V DC

Logic 0 signal (maximum)

5 V DC

Isolation (field side vs logic side)

500 V AC for 1 min

isolation group

2

Number of inputs switched on at the same time

16

cable length

500 m (shielded), 150 m (unshielded)

digital output

output points

16

type

relay, dry contact

voltage range

5 ~ 30 V DC or 5 ~ 250 V AC

Logic 1 signal at maximum current

-

Logic 0 signal with 10 KΩ load

-

Rated current per point (max)

2 A

lamp load

30 W DC/200 W AC

On-state electric shock resistance

0.2 Ω max for new devices

Leakage current per point

-

Inrush current

7 A when the contacts are closed

Overload protection

none

Isolation (field side vs logic side)

1500 V AC for 1 min
    (coil and contacts)
    none (coil and logic side)

Isolation resistance

100 MΩ minimum for new devices

Break the insulation

750 V AC for 1 min

between electric shocks

isolation group

4

Current at each common

8 A

Inductor clamping voltage

-

switch delay

Off to On up to 50 µs
    On to Off up to 200 µs

Mechanical life (no load)

10,000,000 open/close cycles

Electric shock life under rated load

100,000 open/close cycles

Output status in STOP mode

previous value or replacement value (default is 0)

Number of outputs switched on at the same time

16

cable length

500 m (shielded), 150 m (unshielded)


Side View

Dimensions (mm)

Wiring Diagram


If You Would Like to Contact Support or Make a Purchase Please Fill out the Form

If you have urgent needs, please call our customer service number

Please fill in your information in detail so that our support staff can clearly understand your needs.

Value is required
Value is required
Value is required
Value is required
Value is required
Thank you!
UniMAT

EM DR32

View product