model
Technical Parameters
EM DR32
order number
UN 288-2DR32-0AA0
Dimensions W x H x D (mm)
70 x 100 x 81
weight
295.4 g
Power consumption
10 W.
Current consumption (SM bus)
180 mA
Current consumption (24 V DC)
4 mA per input used
11 mA per relay coil used
digital input
Enter the number of points
16
type
sink/source
Rated voltage
24 V DC at 4 mA, nominal
allowable continuous voltage
30 V DC max
surge voltage
35 V DC for 0.5 s
Logic 1 signal (minimum)
15 V DC
Logic 0 signal (maximum)
5 V DC
Isolation (field side vs logic side)
500 V AC for 1 min
isolation group
2
Number of inputs switched on at the same time
16
cable length
500 m (shielded), 150 m (unshielded)
digital output
output points
16
type
relay, dry contact
voltage range
5 ~ 30 V DC or 5 ~ 250 V AC
Logic 1 signal at maximum current
-
Logic 0 signal with 10 KΩ load
-
Rated current per point (max)
2 A
lamp load
30 W DC/200 W AC
On-state electric shock resistance
0.2 Ω max for new devices
Leakage current per point
-
Inrush current
7 A when the contacts are closed
Overload protection
none
Isolation (field side vs logic side)
1500 V AC for 1 min
(coil and contacts)
none (coil and logic side)
Isolation resistance
100 MΩ minimum for new devices
Break the insulation
750 V AC for 1 min
between electric shocks
isolation group
4
Current at each common
8 A
Inductor clamping voltage
-
switch delay
Off to On up to 50 µs
On to Off up to 200 µs
Mechanical life (no load)
10,000,000 open/close cycles
Electric shock life under rated load
100,000 open/close cycles
Output status in STOP mode
previous value or replacement value (default is 0)
Number of outputs switched on at the same time
16
cable length
500 m (shielded), 150 m (unshielded)