model
Technical Parameters
EM DR16
order number
UN 288-2DR16-0AA0
Dimensions W x H x D (mm)
45 x 100 x 81
weight
201.9g
power consumption
5.5W
Current Consumption (SM Bus)
145 mA
Current consumption (24 V DC)
4 mA per point input used
11 mA per relay coil used
digital input
Enter points
8
type
sink/source
Rated voltage
24 V DC at 4 mA, nominal
Allowable continuous voltage
30 V DC max
surge voltage
35 V DC for 0.5 s
Logic 1 signal (minimum)
15 V DC
Logic 0 signal (maximum)
5 V DC
Isolation (field side and logic side)
500 V AC for 1 min
isolation group
2
Simultaneously connected inputs
8
cable length
500 m (shielded), 150 m (unshielded)
digital output
output points
8
type
relay, dry contact
voltage range
5 ~ 30V DC or 5 ~ 250V AC
Logic 1 signal at maximum current
-
Logic 0 signal with 10 KΩ load
-
Rated current per point (maximum)
2A
lamp load
30W DC/200W AC
On-state contact resistance
0.2 Ω max for new devices
Leakage current per point
-
Inrush current
7 A when contacts are closed
overload protection
none
Isolation (field side and logic side)
1500 V AC for 1 min
(coil and contacts)
None (coil and logic side)
isolation resistance
100 MΩ minimum for new devices
Break the insulation between contacts
750 V AC for 1 min
isolation group
isolation group
2
current per common
8A
Inductor Clamp Voltage
-
switch delay
Off-to-on max. 50 µs
On-to-off max. 200 µs
Mechanical life (no load)
10,000,000 open/close cycles
Electric shock life under rated load
100,000 open/close cycles
Output status in STOP mode
previous value or replacement value (default is 0)
Simultaneously connected outputs
8
cable length
500 m (shielded), 150 m (unshielded)