order number
Technical Parameters
UN 288-3AE08-0AA0
physical properties
Dimensions W x H x D (mm)
45 x 100 x 81
power consumption
2W (no load)
Power Characteristics
Rated voltage
DC 24V
Input voltage
DC 20.4 to 28.8V
24V input current
Less than 100mA (no load)
electric shock
12A at 28.8V DC
Insurance
0.75A 60V slow blow
SM bus current
Less than 120mA (single module)
Analog Input Characteristics
Local integrated analog input points
8 inputs
Analog input type
Analog differential input
Voltage Input Range (Bipolar)
±10V,±5V,±2.5V
Current input range
0~20mA
resolution
12 bits
basic error
Voltage input 0.1%FS/0.2%FS
( normal temperature 25°C/limit -0°C~50°C)
Current input 0.2%FS/0.3%FS
Voltage data range
-27648 ~+27648
Current data range
0 ~+27648
overshoot
Voltage: 27,649 ~ 32,511/-27,649 ~ -32,512
Current: 27,649 ~ 32,511/-4864 ~ 0
overflow
Voltage: 32,512 ~ 32,767/-32,513 ~ -32,768
Current: 32,512 ~ 32,767/-4,865 ~ -32,768
input resistance
≥2MΩ voltage input
250Ω current input
Isolation (Field to Logic)
>500V
common mode rejection
40dB , DC to 60Hz
common mode voltage
Signal voltage + common mode voltage ≤ 12V
input voltage
±30V DC (withstanding voltage)
input current
40mA
diagnosis
Overflow/underflow; 24VDC low voltage
Cable length (maximum)
100m , shielded twisted pair
Environment and basic parameters
Working temperature
0 °C~60°C (horizontal installation), 0°C~50°C (vertical installation)
Transport ambient temperature
-20 ℃~80℃
Ambient relative humidity
5 ~ 90%, non-condensing (RH level 2, in line with IEC61131-2)
degree of protection
IP20 , comply with IEC60529
Side View
Wiring Diagram
Structure Diagram
If You Would Like to Contact Support or Make a Purchase Please Fill out the Form
If you have urgent needs, please call our customer service number
Please fill in your information in detail so that our support staff can clearly understand your needs.